2.2kVA / 2200VA / 1920W line interactive 2U rack/tower UPS, Sine Wave

120V output, Corrects brownouts and overvoltages from 83V to 145V

0.9 Power Factor, Interactive LCD interface

Extended runtime options up to 1920W

4 post compatible mounting accessories

96% line-mode efficiency, 2 switched load banks

USB, RS232, EPO and slot for SNMPWEBCARD option

120V NEMA 5-20P input, 4 NEMA 5-15R 4 NEMA 5-15/20R outlets

OUTPUT
Output Capacity Details
Supports 1920 watts in standalone or extended runtime configurations
Output Volt Amp Capacity (VA)
2200
Output kVA Capacity (kVA)
2.2
Output Watt Capacity (Watts)
1920
Output kW Capacity (kW)
1.92
Nominal Output Voltage(s) Supported
120V
Frequency Compatibility
60 Hz
Output Voltage Regulation (Line Mode)
-14%, +6%
Output Voltage Regulation (Battery Mode)
+/- 5%
Output Receptacles
(4) 5-15R (4) 5-15/20R
Load Management Receptacles
Two switched single outlet load banks (1 5-15/20R 1 5-15R)
Output AC Waveform (AC Mode)
Pure Sine wave
Output AC Waveform (Battery Mode)
Pure Sine wave

INPUT
Rated input current (Maximum Load)
16A
Nominal Input Voltage(s) Supported
120V AC
UPS Input Connection Type
5-20P
UPS Input Cord Length (ft.)
10
UPS Input Cord Length (m)
3
Recommended Electrical Service
20A 120V
Input Phase
Single-Phase

BATTERY
Full Load Runtime (min.)
4.5 min. (1920w)
Half Load Runtime (min.)
12 min. (960w)
Expandable Battery Runtime
Extended runtime supported via optional external battery packs
External Battery Pack Compatibility
BP48V24-2U (limit 1) BP48V60RT-3U (multi-pack compatible) BP48V27-2US (multi-pack compatible)
DC System Voltage (VDC)
48
Battery Recharge Rate (Included Batteries)
Less than 4.5 hours from 10% to 90% (typical, full load discharge)

Internal UPS Replacement Battery Cartridge
RBC94-2U
Battery Access
Front panel battery access door
Battery Replacement Description
Hot-swappable, user replaceable batteries
Expandable Runtime
Yes

VOLTAGE REGULATION
Voltage Regulation Description
Automatic voltage regulation (AVR) maintains regulated line power output with an input voltage range of 83 and 145
Overvoltage Correction
Voltage reduction of 12% applies when input is between 127 and 145
Undervoltage Correction
Voltage boost of 12% applies when input voltage is between 96 and 108
Severe Undervoltage Correction
Voltage boost of 24% applies when input voltage is between 83 and 95

USER INTERFACE, ALERTS CONTROLS
Front Panel LCD Display
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)
Switches
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functionsAlarm Cancel Operation
Power-fail alarm can be temporarily silenced using alarm-cancel switch silent mode alarm configuration option available
Audible Alarm
Audible alarm indicates power-failure, overload and low-battery conditions

SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating
570
UPS AC Suppression Response Time
Instantaneous
EMI / RFI AC Noise Suppression
Yes

PHYSICAL
Included Mounting Accessory Description
4 post rackmount installation accessories included
Installation Form Factors Supported with Optional Accessories
2 post rackmount (2POSTRMKITWM) Wallmount (2POSTRMKITWM) Tower (2-9USTAND)
Primary Form Factor
Rackmount
Cooling Method
Fan
UPS Housing Material
Steel

COMMUNICATIONS
Communications Interface
USB (HID enabled) DB9 Serial EPO (emergency power off) Slot for SNMP/Web interface
Network Monitoring Port Description
Supports detailed monitoring of UPS and site power conditions
PowerAlert Software
Included
Communications Cable
USB and DB9 cabling included
WatchDog Compatibility
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility
NUT compatible.

LINE / BATTERY TRANSFER
Transfer Time
5 milliseconds (line to battery mode) 1 millisecond (battery to line mode)
Low Voltage Transfer to Battery Power (Setpoint)
83
High Voltage Transfer to Battery Power (Setpoint)
145

SPECIAL FEATURES
Grounding Lug
Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure)
Cold-start operation supported
High Availability UPS Features
Hot swappable batteries
Green Energy-Saving Features
Greater than 95% efficiency - GREEN UPS Individually controllable load banks

CERTIFICATIONS
UPS Certifications
Tested to UL1778 (USA) Tested to CSA (Canada) Tested to NOM (Mexico) Meets FCC Part 15 Category A (EMI)

Weight
72.00
Item Dimension
9 x 23.6 x 20
Warranty Information
2-year warranty