Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Super-fast switchover from line to battery power occurs within milliseconds to maintain operation of connected equipment without interruption or reboot. 95% line-mode efficiency offers reduced heat emissions and operating costs. USB and RS-232 ports work with PowerAlert software to communicate detailed UPS status and site power conditions. HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Communications ports enable detailed monitoring of equipment load levels, self-test data and utility power conditions. PowerAlert UPS monitoring and control software is available for free download from www.tripplite.com. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode configuration options. Programmable self-test. Field-replaceable, hot-swappable internal batteries.

OUTPUT
Output Volt Amp Capacity (VA):1000
Output kVA Capacity (kVA):1.0
Output Watt Capacity (Watts):700
Power Factor:0.7
Nominal Output Voltage(s) Supported:120V
Frequency Compatibility:60 Hz

Output Voltage Regulation (Line Mode):-21%, +8%
Output Voltage Regulation (Battery Mode):+/- 5%
Output Receptacles:(6) 5-15R
Output AC Waveform (AC Mode):Sine wave
Output AC Waveform (Battery Mode):Pure Sine wave

INPUT
Rated input current (Maximum Load):9.2A
Nominal Input Voltage(s) Supported:120V AC
UPS Input Connection Type:5-15P
Input Circuit Breakers:10A
UPS Input Cord Length (ft.):10

UPS Input Cord Length (m):3
Recommended Electrical Service:15A 120V
Input Phase:Single-Phase

BATTERY
Full Load Runtime (min.):6.4 min. (700w)
Half Load Runtime (min.):15.6 min. (350w)
DC System Voltage (VDC):24
Battery Recharge Rate (Included Batteries):Less than 4.5 hours from 10% to 90% (typical, full load discharge)

Internal UPS Replacement Battery Cartridge:RBC24V-LCD
Battery Access:Front panel battery access door
Battery Replacement Description:Hot-swappable, user replaceable batteries
Expandable Runtime:No

VOLTAGE REGULATION
Voltage Regulation Description:Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 147
Overvoltage Correction:Input voltages between 128 and 147 are reduced by 12%
Undervoltage Correction:Input voltages between 83 and 107 are boosted by 14%

USER INTERFACE, ALERTS and CONTROLS
Front Panel LCD Display:
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, operating mode, alarm function and a variety of additional options (see manual for detailed LCD configuration and monitoring options)

Switches:
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions

Alarm Cancel Operation:
Power-fail alarm can be temporarily silenced using alarm-cancel switch silent mode alarm configuration option available

Audible Alarm:
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating:570
UPS AC Suppression Response Time:Instantaneous
EMI / RFI AC Noise Suppression:Yes

Included Mounting Accessory Description
Includes UPSHDEARKIT for 2 point front-mount and 2 point center-mount rackmount installation in 2 and 4 post racks, plus wallmount installation

Installation Form Factors Supported with Optional Accessories
4 post rackmount (4POSTRAILKIT) Tower (2-9USTAND) Wallmount (2POSTRMKITWM)

Primary Form Factor
Rackmount

Cooling Method
Fan

UPS Housing Material
Steel

COMMUNICATIONS
Communications Interface:DB9 Serial EPO (emergency power off) USB
Network Monitoring Port Description:Supports detailed monitoring of UPS and site power conditions
PowerAlert Software:Available via free download from www.tripplite.com
Communications Cable:USB cabling included

WatchDog Compatibility:
Supports Watchdog application, OS and hard-reboot restart options for remote applications
Network UPS Tools Compatibility:
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.htmlmanufacturerTripp Lite

LINE / BATTERY TRANSFER
Transfer Time:4 milliseconds (AC to battery), 1 milliseconds (Battery to AC)
Low Voltage Transfer to Battery Power (Setpoint):83
High Voltage Transfer to Battery Power (Setpoint):147

SPECIAL FEATURES
Grounding Lug:Back panel grounding lug
Cold Start (Startup in Battery Mode During a Power Failure):Cold-start operation supported
High Availability UPS Features:Hot swappable batteries

CERTIFICATIONS
UPS Certifications:Tested to UL1778 (USA) Tested to CSA (Canada) Tested to NOM (Mexico) Meets FCC Part 15 Category B (EMI)