MPN: PDU3VN6G60C
Category: UPS >> UPS
Vendor: Tripp-Lite
Weight: 18.7 LB(S)
Price: US$ 1641.25
PDU Type
Monitored
Output Capacity Details
18.7kW (240V), 17.9kW (230V), 17.1 (220V), 16.2 (208V), 15.6kW (200V) total capacity 26A max per output phase (L1-L2, L2-L3, L3-L1) 20A max per breakered outlet bank 12A max per C13 outlet
Frequency Compatibility
50 / 60 Hz
Output Receptacles
(36) C13
Output Nominal Voltage
200 /208 /240
Overload Protection
6 20A circuit breakers, 1 per outlet bank
PDU Input Voltage
200 208 240
Recommended Electrical Service
60A 208/240V with IEC309 60A Blue (3P+E) outlet
Maximum Input Amps
45
PDU Plug Type
IEC-309 60A BLUE (3P+E)
Input Cord Length (m)
1.8
Input Phase
3-Phase
Reported Load Segments
Reports input current per phase (L1, L2, L3) and output current for each breakered load bank (B1-B6) Outlets are color-coded and labelled for phase and load bank identification L1-L2 feeds black outlets (B1 B4) L2-L3 feeds dark-gray outlets (B2 B5) L3-L1 feeds light-gray outlets (B3 B6)
Front Panel LCD Display
Large digital display reports Amperage, Kilowatts, Voltage, Unbalance percentage, Temperature and Humidity information (requires ENIVIROSENSE option) Small digital display provides detail on the measurement the large display is reporting: Input-phase (L), Load bank (B), Sensor (S), Load unbalance (UB), Output power (OP)
Front Panel LEDs
Set of 6 LEDs identify the value displayed on the large digital display: Amperage (A), Kilowatts (kW), Voltage (V), Unbalance percentage (%UB), Temperature (T), Humidity (%RH) One additional LED for each output load bank (B1-B6) offers information power availablity: GREEN (<80% load), YELLOW (>80% load), RED (Power OFF), RED FLASHING (Power OFF/breaker trip)
Switches
Set of UP/DOWN arrow buttons scroll through available Input, Bank, Power, Load balance and Sensor options Additional MODE button advances the LEDs to view the next measurement
Material of Construction
Metal
Form Factors Supported
Vertical rackmount installation supported with included mounting brackets supports toolless mounting in button-mount compatible racks
PDU Form Factor
0U Vertical
Operating Temperature Range
32 to 122F (0C to 50C)