MPN: PDU3XVSRHWB
Category: UPS >> UPS
Vendor: Tripp-Lite
Weight: 33 LB(S)
Price: US$ 1364.25
PDU Type
Switched
Output Capacity Details
28.8kW (415/240V), 27.7kW (400/230V), 26.3kW (380/220V) total capacity, 40A max per output phase (L1, L2, L3), 20A max per breakered outlet bank, 16A max per C19 outlet, 12A max (10A CE) per C13 outlet
Frequency Compatibility
50 / 60 Hz
Output Receptacles
(24) C13, (6) C19
Output Nominal Voltage
220 (380V input), 230 (400V input) 240 (415V input)
Overload Protection
6 20A circuit breakers, 1 per outlet bank
PDU Input Voltage
380, 400, 415
Recommended Electrical Service
External circuit breaker - 3 pole, 415V rated minimum, 50A, Wiring - 5C, 8AWG (10mm2), 75C rated minimum Conduit - 3/4 in. (19mm) minimum, flexible
Maximum Input Amps
40
PDU Plug Type
Hardwire
Input Phase
3-Phase
Reported Load Segments
Reports input current per phase (L1, L2, L3), plus output current for each output load bank (B1-B6) and individual output receptacle (1-30), Outlets are color-coded and labelled for phase and load bank identification L1-N feeds black outlets (B1, B4), L2-N feeds dark-gray outlets (B2, B5), L3-N feeds light-gray outlets (B3, B6)
Front Panel LCD Display
Large digital display reports Amperage, Kilowatts, Voltage, Unbalance percentage, Temperature and Humidity information (requires ENIVIROSENSE option) Small digital display provides detail on the measurement the large display is reporting: Input-phase (L), Load bank (B), Sensor (S), Outlet (), Load unbalance % (UB), Output power (OP)
Front Panel LEDs
Set of 6 LEDs identify the value displayed on the large digital display: Amperage (A), Kilowatts (kW), Voltage (V), Unbalance percentage (%UB), Temperature (T), Humidity (%RH) One additional LED for each output receptacle offers power availability information: GREEN (Power ON, load bank capacity <80%), YELLOW (Power ON, load bank capacity >80%), RED (Power OFF/undervoltage), RED FLASHING (Power OFF/breaker trip)
Switches
Set of UP/DOWN arrow buttons scroll through available Input, Bank, Power, Load balance and Sensor options Additional MODE button advances the LEDs to view the next measurement
Material of Construction
Metal
Form Factors Supported
Vertical rackmount installation supported with included mounting brackets supports toolless mounting in button-mount compatible racks
PDU Form Factor
0U, Vertical
Operating Temperature Range
32 to 122oF (0-50oC)
Storage Temperature Range
5 to 140oF (-15 to 60oC)